Auxiliary heat pump control by outdoor temperature 3
External heater output
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Temperature of heater on (Thon): Set temperature (Ts) - 0.9 °F (- 0.5 °C)
Temperature of heater off: Set temperature (Ts) + 0.9 °F (+ 0.5 °C)
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
Tr-Ts
Tr-Ts (=Thon) ≤ -0.9°F (-0.5°C)
Tr-Ts ≥ 0.9°F
(0.5°C)
Auxiliary heat pump On/Off
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of heat pump).
All control temperatures will shift by adjusting “Thon”.
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Off
On
*
Tr-Ts
Tr-Ts ≥ -1.8°F
(-1°C)
Tr-Ts (=Thon) < -5.4°F (-3°C)
*: When room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
Outdoor temperature zone
Heater only zone
Combination zone
(Heat pump + Heater)
Heater only zone
B: 42.8°F (6°C)*
A: -F (-20°C)*
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F (2°C): -0.F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66 and 67
- 45 -
8-5. Details of control output function
8. External input and output
WALL MOUNTED
ASUG09-12LMAS
WALL MOUNTED
ASUG09-12LMAS