¢ Floor/Ceiling type
MODEL: ABYG14LVTA
Outdoor temperature
Indoor temperature (°CDB / °CWB)
18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-10.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
-5.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
0.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
5.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
10.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
15.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
20.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
25.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
30.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
35.0 2.92 1.79 3.51 2.19 3.97 2.49 4.48 3.23 4.79 3.53 4.94 4.04
40.0 2.54 1.36 3.06 1.66 3.45 1.89 3.90 2.44 4.17 2.67 4.29 3.06
46.0 2.16 0.98 2.60 1.20 2.94 1.36 3.31 1.77 3.54 1.93 3.65 2.21
MODEL: ABYG18LVTB
Outdoor temperature
Indoor temperature (°CDB / °CWB)
18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0
(°CDB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
-10.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.12 6.34 5.04
-5.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
0.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
5.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
10.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
15.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
20.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
25.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
30.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
35.0 3.75 2.24 4.51 2.73 5.09 3.11 5.75 4.03 6.15 4.40 6.34 5.04
40.0 3.26 1.69 3.92 2.07 4.43 2.35 5.00 3.05 5.35 3.33 5.51 3.82
46.0 2.77 1.23 3.33 1.49 3.77 1.70 4.25 2.20 4.55 2.41 4.69 2.76
NOTES:
• TC: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
• Values mentioned in the table are based on the following conditions:
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
DESIGN & TECHNICAL MANUAL
- 374 -
OUTDOOR UNIT
AOYG45LBLA6