4. Connection and Settings
Setting the ETERNUS DX/AF
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
44
Setting the ETERNUS DX/AF
Perform the necessary settings for power synchronization by using the setting and maintenance program of the
ETERNUS DX/AF.
ETERNUS AF series, ETERNUS DX S5/S4/S3 series (excluding ETERNUS DX900 S5, ETERNUS
DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3), and ETERNUS DX200F
This section explains the setting items on the power synchronization setting screen.
Figure 11 ETERNUS AF series, ETERNUS DX S5/S4/S3 series (excluding ETERNUS DX900 S5, ETERNUS DX8900
S4, and ETERNUS DX8700 S3/DX8900 S3), and ETERNUS DX200F setup (Setup Power
Management screen)
Auto Power
Select "Disable".
Power Resume
Select "Disable".
If the power synchronized unit and the ETERNUS DX/AF storage system are connected with a redundant configu-
ration, the operations during a power down are as follows:
For the ETERNUS AF series and ETERNUS DX series (excluding the ETERNUS DX900 S5, ETERNUS DX8900 S4,
and ETERNUS DX8700 S3/DX8900 S3)
When the controllers for CM#0 and CM#1 both receive shutdown instructions, the shutdown process starts.
For the ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3
When the Service Controllers (SVC) for SVC#0 and SVC#1 both receive shutdown instructions, the shutdown
process starts.