Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
Copyright 2017 FUJITSU LIMITED P3AM-8012-10ENZ0
46
Auto Power
Select "Disable".
Power Resume
Select "Disable".
Connection CM
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX60 S4/DX100 S4/DX200 S4, ETERNUS DX500
S4/DX600 S4, ETERNUS DX60 S3/DX100 S3/DX200 S3, ETERNUS DX500 S3/DX600 S3, ETERNUS AF250 S2/
AF650 S2, ETERNUS AF250/AF650, and ETERNUS DX200F that are connected to the power synchronized
unit with the RS232C cable.
Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select
"CM#1" when the power synchronized unit is connected to the PWC port on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated
configuration, select both "CM#0" and "CM#1".
Delay until Shutdown
Do not change the default setting (0 minute).
Set management unit interface
Select "Power Synchronized Unit".
Power Failure Signal
"Positive" (positive logic) is automatically set.
Low Battery Signal
"Negative" (negative logic) is automatically set.
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.