Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
Copyright 2017 FUJITSU LIMITED P3AM-8012-10ENZ0
49
■ ETERNUS DX60 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX60 S2.
Figure 4.4 ETERNUS DX60 S2 setup (Setup Power Management screen)
• Enable
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX60 S2 that are connected to the power
synchronized unit with the RS232C cable. Select "CM#0" when the power synchronized unit is connected to
the PWC port on controller 0. Select "CM#1" when the power synchronized unit is connected to the PWC port
on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated
configuration, select both "CM#0" and "CM#1".
• Delay until Shutdown (min.)
Do not change the default setting (0 minute).
• Set management unit interface
Select "Power Synchronized Unit".
• Power Failure Signal
"Positive" (positive logic) is automatically set.
• Low Battery Signal
"Negative" (negative logic) is automatically set.
• UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.