Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
Copyright 2017 FUJITSU LIMITED P3AM-8012-10ENZ0
47
■ ETERNUS DX8700 S3/DX8900 S3
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX8700
S3/DX8900 S3.
Figure 4.2 ETERNUS DX8700 S3/DX8900 S3 setup (Setup Power Management screen)
• Auto Power
Select "Disable".
• Power Resume
Select "Disable".
• Connection SVC
Select the SVCs (SVC#0 and/or SVC#1) of the ETERNUS DX8700 S3/DX8900 S3 that are connected to the
power synchronized unit with the RS232C cable.
Select "SVC#0" when the power synchronized unit is connected to the PWC port on SVC#0. Select "SVC#1"
when the power synchronized unit is connected to the PWC port on SVC#1.
When different power synchronized units are connected to SVC#0 and SVC#1 in a duplicated configuration,
select both "SVC#0" and "SVC#1".
• Delay until Shutdown
Do not change the default setting (0 minute).
• Set management unit interface
Select "Power Synchronized Unit".
• Power Failure Signal
"Positive" (positive logic) is automatically set.
• Low Battery Signal
"Negative" (negative logic) is automatically set.
• UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.