Chapter 4 Connection and Settings
4.4 Connecting to the Server UPS Unit
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
Copyright 2017 FUJITSU LIMITED P3AM-8012-10ENZ0
60
3 When two or more AC sensor units are connected, connect the AC sensor units with the AC
sensor port connection cables.
3-1 Connect the AC sensor port connection cable to the other port on the branch connector.
3-2 Connect the connector at the other end of the AC sensor port connection cable to another AC sensor
unit.
• Up to 14 AC sensor units can be connected.
• Do not attach a termination resistor to the branch connector on the AC sensor unit. Doing so
makes operations unstable.
AC sensor port connection cable
AC sensor port connection cable
Branch connector