Chapter 2 Preparing to Install the Server 2-3
The environmental requirements to run the server might vary depending on the
elevation as listed in
TABLE 2-1.
TABLE 2-2 lists the recommended values for the temperature and humidity in the
computer room.
TABLE 2-1 Ambient Environmental Requirements
Operating Range Non-Operating Range Optimum
Ambient
temperature
5˚C to 35˚C
(41˚F to 95˚F)
Unpacked
0˚C to 50˚C (32˚F to 122˚F)
Packed:
-20˚C to 60˚C (-4˚F to 140˚F)
21˚C to 23˚C
(70˚F to 74˚F)
Relative
humidity
*
* There is no condensation regardless of the temperature and humidity
20% RH to 80% RH to 93% RH 45% RH to 50% RH
Altitude
restriction
All altitudes are above sea level.
3,000m (10,000 ft) 12,000m (40,000 ft)
Temperature
conditions
5˚C to 35˚C (41˚F to 95˚F)
0 m to 500 m (0 ft to 1,640 ft)
5˚C to 33˚C (41˚F to 91.4˚F)
501 m to 1,000 m (1,644 ft to 3,281 ft)
5˚C to 31˚C (41˚F to 87.8˚F)
1,001 m to 1,500 m (3,284 ft to 4,921 ft)
5˚C to 29˚C (41˚F to 84.2˚F)
1,501 m to 3,000 m (4,925 ft to 9,843 ft)

Table of Contents

Other manuals for Fujitsu SPARC Enterprise M3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu SPARC Enterprise M3000 and is the answer not in the manual?

Fujitsu SPARC Enterprise M3000 Specifications

General IconGeneral
BrandFujitsu
ModelSPARC Enterprise M3000
CategoryServer
LanguageEnglish

Related product manuals