EasyManua.ls Logo

Fujitsu WATERSTAGE 112 - 6.3.13 Input; Output Testing Functions

Fujitsu WATERSTAGE 112
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heat Pump, Split System, Single Service, 3 phase
Maintenance Document 1394-1 103
6.3.13 Input / Output Testing Functions
Input/output testing is used to ensure that the
connected components are in working order.
Relay Output Testing
Selection of a setting from relay testing closes the
corresponding relay and therefore switches on the
connected component. This makes it possible to
check that the relays are in working order and that
the wiring has been performed correctly.
Line no. Programming line
7700 Relay test
(No test / All OFF / Relay output QX23 Module 1 / Relay output QX21 module 1 / Relay output QX22
module 1 / Relay output QX1 / Relay output QX2 / Relay output QX3 / Relay output QX4 / Relay output
QX5 / Relay output QX6 / Relay output QX23 Module 2 / Relay output QX21 Module 2 / Relay output
QX22 Module 2 / Relay output QX7)
Warning:
During testing of an output, the heat pump is stopped,
all outputs are "off" and only the controlled output is
on.
Analog Input/Output Testing
Line no. Programming line
7710 Output test UX
7711 Voltage signal UX
7720 Digital output test
7721 Digital output DO1
7722 Digital output DO2
Output test UX
Enables testing the outdoor unit control.
Voltage signal UX
Displays the voltage value at the UX output.
Digital output test
Enables testing outputs DO1 and DO2
Digital output DOx
Shows the output status.
Sensor Input Testing
Line no. Programming line
7730 Outside temp B9
7820 Sensor temp BX1
7823 Sensor temp BX4
7824 Sensor temp BX5
7830 Sensor temp BX21 module 1
7831 Sensor temp BX22 module 1
7832 Sensor temp BX21 module 2
7833 Sensor temp BX22 module 2
Displays the temperature of each sensor.
H1, H2, H3 Input Testing
Line no. Programming line
7841 Contact state H1
7846 Contact state H2
7855 Contact state H3
Displays the momentary status of contact Hx.

Table of Contents