Heat Pump, Split System, Single Service, 3 phase
6 Maintenance Document 1394-1
1 Technical Characteristics
1.1 Specifications
Heating system operating limits
WATERSTAGE
112
WATERSTAGE
140
WATERSTAGE
160
Exterior temp mini/maxi °C -20/+35
Initial max heating water temperature
- Floor heating system °C 45
- Low temperature radiator °C 60
Flow min heating water temperature °C 8
1.2 Performance Data
1.2.1 Rated Performance
HEAT PUMP
WATERSTAGE
112
WATERSTAGE
140
WATERSTAGE
160
P
out
(kW) 11,2 14,00 16,00
P
in
(kW) 2,51 3,22 3,72
+ 7°C/ + 35°C
-
HCF COP 4,46 4,35 4,30
P
out
(kW) 11,2 14,00 15,00
P
in
(kW) 3,92 5,15 5,55
- 7°C/ + 35°C
-
HCF COP 2,86 2,72 2,70
P
out
(kW) 10,5 13,1 15,1
P
in
(kW) 2,9 3,7 4,42
+ 7°C/ + 45°C
-
LT Radiators COP 3,62 3,54 3,42
P
out
(kW) 10,5 13,1 14,5
P
in
(kW) 4,16 5,39 6,38
- 7°C/ + 45°C
-
LT Radiators COP 2,52 2,43 2,27
1.2.2 Maximum Stated Performance
HEAT PUMP
WATERSTAGE
112
WATERSTAGE
140
WATERSTAGE
160
P
out
(kW) 20,26 21,91 23,39
P
in
(kW) 5,06 5,75 6,5
+ 7°C/ + 35°C
-
HCF COP 4,00 3,81 3,60
P
out
(kW) 17,09 18,67 20,20
P
in
(kW) 5,04 5,67 6,43
+ 7°C/ + 45°C
-
LT Radiators COP 3,39 3,29 3,14