EasyManua.ls Logo

Fujitsu WATERSTAGE 112 - Annual Maintenance Services; 7.1 Hydraulic Circuit; 7.2 Outdoor unit; 7.3 Electrical

Fujitsu WATERSTAGE 112
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heat Pump, Split System, Single Service, 3 phase
Maintenance Document 1394-1 113
7 Annual Maintenance Services
7.1 Hydraulic Circuit
clean filter (if any)
inspect heating system (system pressure,
purging, leak test)
inspect expansion vessel (preload with nitrogen
at 1 bar)
fix any leaks
7.2 Outdoor unit
clean heat exchanger
clean refrigeration and ventilation compartment
check for correct condensation drain
conduct refrigeration circuit leak test (required if
charged > 2 kg)
7.3 Electrical
Inspect connections and tighten where
appropriate
Check condition of wires and boards
7.4 Operating checks
conduct refrigeration readings at temperatures
in case of malfunction, install pressure gauges
for refrigeration diagnosis
check voltage, current and control

Table of Contents

Related product manuals