Heat Pump, Split System, Single Service, 3 phase
Maintenance Document 1394-1 63
6 Control Settings
6.1 General
The settings described below are those which can be
modified by the user.
We wish to remind you that changing the settings
below may cause the heat pump to behave in an
undesirable way. A testing period should be
conducted before the permanent settings of the heat
pump are confirmed. This may require a number of
changes to be made by the installer.
There are 4 access levels:
U: end-user level
I: commissioning level (installer start-up)
S: engineer level (specialist)
C: OEM level (manufacturer) (not available)
6.2 Function Table
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
Time of day and date
1 U Hour/minutes 00:00…23:59
2 U Day/month 01.01…31.12
3 U Year 1900…2099
5 S Start of summertime 01.01…31.12 25.03
6 S End of summertime 01.01…31.12 25.10
Operator section
20 U Language English
22 S Info
Temporarily /
Permanent
Temporarily
26 S Operation lock Off/on Off
27 S Programming lock Off/on Off
28 I Direct adjustment Auto/confirm Confirm
40* I Used as
Room unit 1
Room unit 2
Room unit P
User interface 1
User interface 2
User interface P
Operating unit
Room unit 1
42* I Assignement device 1
44 I Operation HC2
Commonly with HC1
46 I Operation HCP
Commonly with HC1
48* I Operator occupancy button
None
Heating circuit 1
Heating circuit 2
Shared
None
54* I Readjustment room sensor
70 S Software version
Time prog heating circuit 1
500 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
501 U 1
st
phase on 00:00…--:-- 6:00
502 U 1
st
phase off 00:00…--:-- 22:00
503 U 2
nd
phase on 00:00…--:-- --:--
504 U 2
nd
phase off 00:00…--:-- --:--
505 U 3
rd
phase on 00:00…--:-- --:--
506 U 3
rd
phase off 00:00…--:-- --:--
516 U Default values No/yes No
Time prog heating circuit 2
520 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
521 U 1
st
phase on 00:00…--:-- 6:00
522 U 1
st
phase off 00:00…--:-- 22:00