Heat Pump, Split System, Single Service, 3 phase
64 Maintenance Document 1394-1
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
523 U 2
nd
phase on 00:00…--:-- --:--
524 U 2
nd
phase off 00:00…--:-- --:--
525 U 3
rd
phase on 00:00…--:-- --:--
526 U 3
rd
phase off 00:00…--:-- --:--
536 U Default values No/yes No
Time program 4 / DHW
560 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
561 U 1
st
phase on 00:00…--:-- 00:00
562 U 1
st
phase off 00:00…--:-- 05:00
563 U 2
nd
phase on 00:00…--:-- --:--
564 U 2
nd
phase off 00:00…--:-- --:--
565 U 3
rd
phase on 00:00…--:-- --:--
566 U 3
rd
phase off 00:00…--:-- --:--
576 U Default values No/yes No
Time program 5 / Cooling circuit
600 U Preselection
Mon-Sun ¦ Mon-Fri ¦ Sat - Sun ¦
Mon ¦ Tue ¦ Wed ¦Thu ¦ Fri ¦ Sat
¦Sun
Mon-Sun
601 U 1
st
phase on 00:00…--:-- 8:00
602 U 1
st
phase off 00:00…--:-- 20:00
603 U 2
nd
phase on 00:00…--:-- --:--
604 U 2
nd
phase off 00:00…--:-- --:--
605 U 3
rd
phase on 00:00…--:-- --:--
606 U 3
rd
phase off 00:00…--:-- --:--
616 U Default values No/yes No
Holidays heating circuit 1
641 U Preselection Period 1…8 Period 1
642 U Start 01.01…31.12
643 U End 01.01…31.12
648 U Operating level
Frost protection ¦ Reduced Frost protection
Holidays heating circuit 2
651 U Preselection Period 1…8 Period 1
652 U Start 01.01…31.12
653 U End 01.01…31.12
658 U Operating level
Frost protection ¦ Reduced Frost protection
Heating circuit 1
710 U Comfort heating setpoint
Reduced temp to
35°C
20°C
712 U Reduced setpoint 18°C
714 U Frost protection setpoint
4°C to Reduced
temp
8°C
716 S Comfort setpoint max 20°C…35°C 28°C
720 I Heating curve slope 0,1…4 0,5
721 I Heating curve displacement -4,5°C…4,5°C 0°C
726 I Heating curve adaptation Off, on Off
730 I Summer/winter heating limit 8°C…30°C 18°C
732 S 24-Hour heating limit -10°C…10°C -3°C
740 S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C 8°C
741 S Flow temp setpoint max 8°C… 95°C 55°C
Floor heating system = 50 °C / Higher temperature radiator = 65 °C
750 S Room influence 1%...100% 20%
790 S Optimum start control max 0…360min 120 min
791 S Optimum stop control max 0…360min 120 min
800 S Reduced setpoint increase start -30°C…10°C ---
801 S Reduced setpoint increase end -30°C…10°C -5°C
830 S Mixing valve boost 0…50°C 0