Heat Pump, Split System, Single Service, 3 phase
Maintenance Document 1394-1 65
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
834 S Actuator running time 30…873s 240s
850 I Floor curing function 0…5 Off
851 I Floor curing setpoint manually 0°C…95°C 25°C
856 I Floor curing day current 0…32
857 I Floor curing days completed 0…32
900 S Optg mode changeover
Protection mode
Cooling circuit 1
901 U Operating mode
Off … automatic
Off
902 U Comfort cooling setpoint 17…40 24°C
907 U Release
24h/day
Heating circuit time pgm
Time program 5
Time program 5
908 I Flow temp setp at OT 25°C 6…35°C 20°C
909 I Flow temp setp at OT 35°C 6…35°C 16°C
912 I Cooling limit at OT 8…35°C 24°C
913 S Lock time after end of heating 8…100h 24h
918 S Summer comp start at OT 20…50°C 26°C
919 S Summer comp end at OT 20…50°C 40°C
920 S Summer comp setp increase 1…10°C 4°C
923 S Flow temp setp min at OT 25°C 6…35°C 18°C
924 S Flow temp setp min at OT 35°C 6…35°C 18°C
928 S Room influence 1…100% 80%
932 S Room temperature limitation 0,5…4°C 0,5°C
938 S Mixing valve decrease 0…20°C 0°C
941 S Actuator running time 30…873s 240s
945 S Mixing valve in heating mode
Control
Open
Control
946 S Lock time dewpoint limiter 10…600min 60min
947 S Flow temp setp incr hygro 1…20°C 10°C
948 S Flow setp incr start at r.h. 0…100% 60%
950 S Flow temp diff. dewpoint 0…5°C 2°C
963 S With prim contr/system pump
No
Yes
No
969 S Optg mode changeover
None ; Off ; Automatic
Off
Heating circuit 2
1010 U Comfort heating setpoint
Reduced temp to
35°C
20°C
1012 U Reduced setpoint 18°C
1014 U Frost protection setpoint
4°C to Reduced
temp
8°C
1016 S Comfort setpoint max 20…35°C 28°C
1020 I Heating curve slope 0,1…4 0,5
1021 I Heating curve displacement
-4,5°C…4,5°C
0°C
1026 S Heating curve adaptation Off, on Off
1030 I Summer/winter heating limit 8°C…30°C 18°C
1032 S 24-Hour heating limit -10°C…10°C -3°C
1040 S
Flow temp setpoint min (for fan
convectors)
8°C… 95°C 8°C
1041 S Flow temp setpoint max 8°C… 95°C 55°C
Floor heating system = 50 °C / Higher temperature radiator = 65 °C
1050 S Room influence 1%...100% 20%
1090 S Optimum start control max 0…360min 120 min
1091 S Optimum stop control max 0…360min 120 min
1100 S Reduced setpoint increase start -30…10°C ---
1101 S Reduced setpoint increase end -30…10°C -5°C
1130 S Mixing valve boost 0…50°C 0°C
1134 S Actuator running time 30…873s 240s
1150 I Floor curing function 0…5 0
1151 I Floor curing setpoint manually 0°C…95°C 25°C