EasyManua.ls Logo

Fujitsu WATERSTAGE 112 - Page 128

Fujitsu WATERSTAGE 112
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Heat Pump, Split System, Single Service, 3 phase
128 Maintenance Document 1394-1
2284Z33a
2284Z34a
2284Z35a
Connection:
The room thermostat must be connected to one of
the terminals b (CL+, CL-) of the heat pump controller
board. To do this, you can use a 0.5mm² cable of the
two-pair telephone cable type.
If the cable is shielded, the shielding can be
connected to the controller CL- terminal. It may under
no circumstances be connected on both sides, i.e.
controller side and room unit side.
If the installation is equipped with 2 room
thermostats, the second thermostat must be
connected to the second terminal block b.
Configuration:
Gain access to the settings by continuously pressing the "Heating mode" key
fs = 1 (factory setting) Æ The room unit is addressed as ZONE 1
fs = 2 Æ The room unit is addressed as ZONE 2
fs = 3 Æ The room unit is addressed as ZONE 3 (factory setting)
P1 = 1 (factory setting) Automatic save:
Correction of the setpoint using the knob is accepted without special confirmation (timeout) or by pressing the
operating mode key.
P1 = 2 Confirm save
Correction of the setpoint with the knob is accepted only after pressing the operating mode key.
1 CL+
2 CL-
1
34
562
2284 Z40
User interface

Table of Contents

Related product manuals