Heat Pump, Split System, Single Service, 3 phase
Maintenance Document 1394-1 49
Clear 36: No voltage on outdoor unit
Probable causes:
Power supply fault.
External cause.
Faulty electrical components.
Check:
3. Check the electrical components:
2. Check for external causes on the Hydraulic Unit and outdoor unit (noise or voltage drop) :
- Check for any other electrical device on the same electric circuit which might cause a drop in
voltage.
- Check for any current leaks.
- Check for any equipment generating electromagnetic waves which interfere with the
communication between the Hydraulic Unit and the outdoor unit.
OK
OK
1. Check the installation
- Is the circuit breaker cut off?
- Check the wiring.
NO
If all of these checks are unsuccessful, replace Filter PCB, Main PCB,
Inverter PCB and PFC PCB.
OK
- Check that a voltage between AC 198 and AC 264 V exists between terminals 1 and 2 on the
Hydraulic Unit terminal block.
- Check Main PCB (power supply) for :
o either the fuse (F1, F3).
o or the varistor (VA1-VA5). Fault: overvoltage - external causes - power supply to be
checked).
- Replace the faulty component (if the varistor is blown, the PCB must be replaced).
YES