Heat Pump, Split System, Single Service, 3 phase
68 Maintenance Document 1394-1
COMMAND
LINE
ACCESS
LEVEL
FUNCTION SETTING RANGE
FACTORY
SETTING
7711 I Voltage signal UX 0…10volt 0 volt
7720 I Digital output test
No test
All OFF
Digital output DO1
Digital output DO2
No test
7721 I Digital output DO1
Cooling mode
Heating mode
Heating mode
7722 I Digital output DO2 On/off Off
7730 I Outside temp B9 -50…50°C 0°C
7820 I Sensor temp BX1 -28…350°C 0°C
7823 I Sensor temp BX4 -28…350°C 0°C
7824 I Sensor temp BX5 -28…350°C 0°C
7830 I Sensor temp BX21 module 1 -28…350°C 0°C
7831 I Sensor temp BX22 module 1 -28…350°C 0°C
7832 I Sensor temp BX21 module 2 -28…350°C 0°C
7833 I Sensor temp BX22 module 2 -28…350°C 0°C
7841 I Contact state H1 Open/closed Open
7846 I Contact state H2 Open/closed Open
7855 I Contact state H3 Open/closed Open
7914 I Input Ex4 0/230V 0
7915 I Input Ex5 0/230V 0
7916 I Input Ex6 0/230V 0
State of plant
8000 I State heating circuit 1 0
8001 I State heating circuit 2 0
8003 I State DHW 0
8004 I State cooling circuit 1 0
8006 I State heat pump 0
8011 I State swimming pool 0
8022 I State supplementary source 0
8050 I History 1 Date/time/code
8052 I History 2 Date/time/code
8054 I History 3 Date/time/code
8056 I History 4 Date/time/code
8058 I History 5 Date/time/code
8060 I History 6 Date/time/code
8062 I History 7 Date/time/code
8064 I History 8 Date/time/code
8066 I History 9 Date/time/code
8068 I History 10 Date/time/code
Diagnostics heat source
8402 I El imm heater 1 flow Off/on Off
8403 I El imm heater 2 flow Off/on Off
8406 I Condenser pump Off/on Off
8410 U Return temp HP 0…140°C 0°C
8411 U Setpoint HP 0…140°C 0°C
8412 U Flow temp HP 0…140°C 0°C
8413 U Compressor modulation 0…100% 0%
8425 I Temp diff condenser -50…140°C 0°C
8454 S Locking time HP 0…2730h 00:00:00
8455 S Counter number of locks HP 0…65535 0
8456 S Hours run el flow 0…2730h 00:00:00
8457 S Start counter el flow 0…65535 0
Diagnostics consumers
8700 U Outside temperature -50…50°C 0°C
8701 U Outside temp min -50…50°C 50°C
8702 U Outside temp max -50…50°C -50°C
8703 I Outside temp attenuated -50…50°C 0°C
8704 I Outside temperature composite -50…50°C 0°C