78 Maintenance Document 1394-1
The influence of the difference is defined as a
percentage. The better the installation in the
reference room (accurate room temperature, correct
installation location, etc.) the higher will be the value
that can be set.
Example:
Approx 60%: the reference room is appropriate
Approx 20 %: the reference room is inappropriate
Information:
Activation of the function requires taking into account
the following requirements:
- A room sensor must be connected.
- The "room influence" parameter must be set
between 1 and 99.
- The reference room (where the room sensor
is installed) must not contain adjusted thermostatic
valves. If present in the room, these valves must be
fully open.
Control according to room temperature only
The flow temperature is adjusted according to the
room temperature setpoint, the current room
temperature and its evolution. A slight increase in
room temperature, for example, causes an immediate
drop in the flow temperature.
Information:
Activation of the function requires taking into account
the following requirements:
- A room sensor must be connected.
- The "room influence" parameter must be set
to 100%.
The reference room (where the room sensor is
installed) must not contain adjusted thermostatic
valves. If present in the room, these valves must be
fully open.