Page 24 of 35 GTLE Error list GTLE Operating Manual
Message-
number
Sensor-/
actuator
Messagetext Reason Action
15 F2 fuse F2 blown, short cut/fault at inputs Kurschluss bei den Eingängen liegt vor
Check the sensors for a short circuit somewhere and fix it. After
eliminating the error, the fuse is automatically reset.
16 F3 fuse F3 blown, short cut/fault at charging Short circuit during charging has occurred
Check whether the charging contact has caused a short circuit
somewhere and fix it. After eliminating the error, the backup is
17 F4 fuse F4 blown, short cut/fault at outputs Short-circuit at outputs has occurred.
Check whether there is a short circuit in an actuator and replace
the glass tube fuse on the control.
Plausibility check error (S15)
Switch position NC and NO contacts do not match.
Checking the wiring at switch S15
19 S16 Plausibility check error (S16) Switch position NC and NO contacts do not match. Checking the wiring at switch S16
20 - Two activations at one time
Two commands are received from the controller.
Two commands simultaneously from local control
or two commands from radio control
Check whether a second key has been pressed. Otherwise
check the cabling of the buttons.
21 - Lift move over remote locked
The lift ride is parameterised in the menu so that
driving with an open or closed platform is not
permitted.
Contact service technician why it is blocked.
22 ZS1
Counter sensor error (ZS1), does not
The counting sensor ZS1 no longer detects any
Check the sensor to see if it still switches.
23 - Folding in this landing locked Platform movement is blocked at this stop Contact service technician why it is blocked.
24 K9 Relay error K9
Feedback from contactor K9 does not match the
Error on the motherboard. Switch the lift off and on again. If the
error persists, contact your service technician.