Page 74
7SPECIFICATION & RECORDS
GardT
ec
872 Control Panel Specification
Power Input 230V a.c +/- 10% @ 50Hz
Max Loop Resistance 2K (not with E.O.L)
Loop Delay Time 600 milliseconds
FUSES
Bell 1A Quick Blow
R.K.P 500mA Quick Blow
Aux 1A Anti-surge
Gard 400mA Quick Blow
Mains 125mA Anti-surge
Low Voltage Output 13.8 Regulated
Battery Sizes 12V 1.2A, 2.0A, 3.0A, 7.0A
Construction 3mm Polycarbonate
or
1.2mm Mild Steel
Complies With BS 4737 Parts 1 & 2
CE tested
Conforms with EMC Directive 89/336/EEC & LVD Directive 73/23/EEC
Number Of Zones
(Standard) 8 (4 Wire), 16 (E.O.L or 2 Wire)
Expandable To 80 (4 Wire), 144 (EOL or 2 Wire)
Expansion Type Expander Cards with 4 (4 Wire) per card
Zones or 8 (E.O.L or 2 Wire) per card
Zones Per Card
1 Radio Expander may be fitted allowing 2 Receivers may
be fitted in place of Expander 8 &16 (if required)
or
ID Expander Cards (Max2)
30 ID zones per Expander
(Panel zones as normal)
Radio Expander cannot be used with ID
872.qxd 05/11/2003 15:01 Page 74