Page 60
490X Engineer’s Reference Guide
Programming Panic
Note: Duress is defaulted to Off and cannot be changed. Duress 7 is now no
longer available.
You should also check current legislation if Panic signals are allowed for the grade of
system that you are fitting.
1) Enter into Engineer Mode
To do this follow Steps 1 to 4 on page 18
With the display showing:-
2) Press No seven times. The display will show:-
3) Press Yes. The display will show:-
It should be noted that with PA = Bells Only no PA signals will be sent to Central
Station.
Available setting for PA are
Bells Only Activating a Panic will only sound the Bells.
Bells Always Activating a Panic will Sound the Bells and send a signal
to Central Station provided that a Digi Channel is
programmed as Panic.
Silent Always Activating a Panic will only send a signal to Central Station
providing that a Digi Channel has been programmed as
Panic.
Bells if LFlt As Silent Always but will revert to Bells if a Linefault is
present.
Program . . . . _ _ _
Zones ?
Program . . . . _ _ _
Panic / Duress ?
PA = Bells Only
= Non-Testable