Page 84
490X Engineer’s Reference Guide
c) Scenario Opening the initial entry door disables all means of
conformation 6.4.4 DD243 2002.
Event 1 System Set
Event 2 Entry Door Opened (entry time starts) Confirmed Alarms
Disabled
Event 3 Entry Time Expires (inc Entry Time 2) Unconfirmed Alarm
Transmitted
Event 4 Any subsequent zones triggered No Confirmed Signals
Transmitted
To achieve the above
Confirmed on entry = Off
Programming Alarm Confirm
1) Enter into Engineer Mode
To do this follow Steps 1 to 4 on page 18
With the display showing:-
2) Press No sixteen times. The display will show:-
3) Press Yes. The display will show:-
4) Press Yes. The display will show:-
5) Press No twice. The display will show:-
6) Enter the time you require followed by Yes.
The time MUST be between 30 & 60 minutes
Program . . . . _ _ _
Zones ?
Program . . . . _ _ _
Alarm Confirm ?
Program Confirm
Window Time ?
Confirm Window
= 060m
Confirm Window
> _ _ _m