12–6 EPM 9450/9650 ADVANCED POWER QUALITY METERING SYSTEM – INSTRUCTION MANUAL
FLICKER POLLING SCREEN CHAPTER 12: FLICKER AND ANALYSIS
12.4 Flicker Polling Screen
From the GE Communicator Title bar, select Real-Time Poll > Power Quality and
Alarms > Flicker. You will see the screen shown below.
Main screen
This section describes the Main Screen functions. These functions are found on the left side
of the screen.
Time
Start/Reset is the time when Flicker was started or reset. A Reset of Flicker causes
the Max/Min values to be cleared and restarts the Flicker Pst and Plt timers. A Start
of Flicker is also equivalent to a Reset in that the Pst and Plt are restarted and the
Max/Min Values are cleared.
Stop corresponds to the time when Flicker is turned off.
Current is the current clock time.
Next Pst is the countdown time to when the next Pst value is available.
Next Plt is the countdown time to when the next Plt value is available.
Status
This screen indicates the current status: Active = On; Stopped = Off.
Frequency
Base is the operating frequency (50 or 60 Hz) selected in the EN50160 Flicker
screen (see Section 12.3).
Current is the real-time frequency measurement of the applied voltage.
Base Voltage
This field shows the normalized voltage for the selected frequency (230 V for 50 Hz
or 120 V for 60 Hz).