2–16 EPM 9450/9650 ADVANCED POWER QUALITY METERING SYSTEM – INSTRUCTION MANUAL
EPM P40N
PLUS
LED EXTERNAL DISPLAY SPECIFICATIONS CHAPTER 2: METER OVERVIEW
2.10 EPM P40N
PLUS
LED External Display Specifications
Maximum Input Voltage:............30VDC
Minimum Input Voltage: ............12VDC
Maximum Power Consumption:5W
Nominal Power Consumption:.Approximately 3W
Operating Temperature Range: -20 to +70
o
C/-4 to +158
o
F
Overall Dimensions (HxWxD): .5.25 x 5.25 x1.79 inches/13.34 x 13.34 x 4.54 cm
(The legacy P40N dimensions are 4.4 x 4.4 x 2.2 inches/11.1 x 11.1 x
5.9cm)
2.11 EPM P60N LCD External Display Specifications
Maximum Input Voltage:............30VDC
Minimum Input Voltage: ............10VDC
Maximum Power Consumption:5W
Nominal Power Consumption:.Approximately 4.5W
Operating Temperature Range: 0 to 50
o
C/32 to 122
o
F
Overall Dimensions (HxWxD): .1.6 x 5.4 x 8.0 in / 4.0 x 13.7 x 20.3 cm
2.12 Upgrading the EPM 9650 Meter’s Software Option
The EPM 9650 meter’s base configuration is Software Option "A". To upgrade your meter to
support flicker with 4 MB (Software Option "B"), follow these steps:
1. Obtain an upgrade key by contacting GE sales staff at
sales@gridsolutions.ge.com or by calling +1 905 927 7070. You will be asked
for the following information:
• Serial number(s) of the meter you are upgrading.
• Desired upgrade.
• Credit card or Purchase Order number.
2. GE will issue you the upgrade key. To enable the key, follow these steps:
• Open the GE Communicator software.
• Power up your EPM 9650 meter.
• Connect to the meter via GE Communicator. (See the GE Communicator
Instruction Manual for detailed instructions. You can open the manual
online by clicking Help > Contents from the GE Communicator Main
screen).
• Click Tools > Upgrade from the Title Bar of the Main screen. A screen
opens, requesting the encrypted key.
• Enter the upgrade key provided by GE.
• Click OK. The key is enabled and the meter is reset.
NOTE
Note
The EPM 9450 meter does not have a software option upgrade available.