EPM 9450/9650 ADVANCED POWER QUALITY METERING SYSTEM – INSTRUCTION MANUAL 3–1
EPM 9450/9650
Chapter 3: Hardware Installation
GE
Grid Solutions
Hardware Instal lation
This chapter provides installation information for the EPM 9450/9650 meter and its
optional modules and displays.
3.1 Mounting the EPM 9450/9650 Meter
The EPM 9450/9650 Meter is designed to mount against any firm, flat surface. Use a #10
screw in each of the four slots on the flange to ensure that the unit is installed securely. For
safety reasons, mount the meter in an enclosed and protected environment, such as in a
switchgear cabinet. Install a switch or circuit breaker nearby; label it clearly as the meter’s
disconnecting mechanism.
Note
The EPM 9450/9650 meter with the Internal Modem Option mounts the same way.
Maintain the following conditions:
• Operating Temperature: -40°C to +70°C / -40°F to +158°F
• Storage Temperature: -40°C to +70°C / -40°F to +158°F