CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-245
71621 0x7B84 Dropout Delay 0 6000000 1 s F13 0 2 Y
71623 0x7B86 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
71625 0x7B88 Block 0 0xC6CD00 1 FC142 0 2 Y
71627 0x7B8A Events 0 1 1 FC126 1 1 Y
71628 0x7B8B Targets 0 2 1 FC101 1 1 Y
Ground IOC 12
71642 0x7B99 Function 0 4 1 FC100 0 1 Y
71643 0x7B9A Signal Input 1 5 1 FC102A 1 1 Y
71645 0x7B9C Pickup 50 30000 1 x CT F13 1000 2 Y
71647 0x7B9E Direction 0 2 1 FC164 0 1 Y
71648 0x7B9F Pickup Delay 0 6000000 1 s F13 0 2 Y
71650 0x7BA1 Dropout Delay 0 6000000 1 s F13 0 2 Y
71652 0x7BA3 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
71654 0x7BA5 Block 0 0xC6CD00 1 FC142 0 2 Y
71656 0x7BA7 Events 0 1 1 FC126 1 1 Y
71657 0x7BA8 Targets 0 2 1 FC101 1 1 Y
Ground Directional OC 1
71803 0x7C3A Function 0 1 1 FC126 0 1 Y Y Y
71804 0x7C3B Signal Input 1 5 1 FC102A 1 1 Y Y Y
71805 0x7C3C Polarizing Mode 1 3 1 FC156 1 1 Y Y Y
71806 0x7C3D Polarizing Voltage 0 1 1 FC272 0 1 Y Y Y
71808 0x7C3F Forward ECA -90 90 1 ° F20 75 1 Y Y Y
71809 0x7C40 Forward Limit Angle 40 90 1 ° F0 90 1 Y Y Y
71810 0x7C41 Forward Pickup 50 30000 1 x CT F3 50 1 Y Y Y
71811 0x7C42 Reverse Limit Angle 40 90 1 ° F0 90 1 Y Y Y
71812 0x7C43 Reverse Pickup 50 30000 1 x CT F3 50 1 Y Y Y
71813 0x7C44 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y
71815 0x7C46 Events 0 1 1 FC126 1 1 Y Y Y
71816 0x7C47 Targets 0 2 1 FC101 1 1 Y Y Y
Ground Directional OC 2
71830 0x7C55 Function 0 1 1 FC126 0 1 Y
71831 0x7C56 Signal Input 1 5 1 FC102A 1 1 Y
71832 0x7C57 Polarizing Mode 1 3 1 FC156 1 1 Y
71833 0x7C58 Polarizing Voltage 0 1 1 FC272 0 1 Y
71835 0x7C5A Forward ECA -90 90 1 ° F20 75 1 Y
71836 0x7C5B Forward Limit Angle 40 90 1 ° F0 90 1 Y
71837 0x7C5C Forward Pickup 50 30000 1 x CT F3 50 1 Y
71838 0x7C5D Reverse Limit Angle 40 90 1 ° F0 90 1 Y
71839 0x7C5E Reverse Pickup 50 30000 1 x CT F3 50 1 Y
71840 0x7C5F Block 0 0xC6CD00 1 FC142 0 2 Y
71842 0x7C61 Events 0 1 1 FC126 1 1 Y
71843 0x7C62 Targets 0 2 1 FC101 1 1 Y
Sensitive Ground TOC 1
71923 0x7CB2 Function 0 4 1 FC100 0 1 Y Y
71925 0x7CB4 Input 0 1 1 FC256 0 1 Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5