13-246 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
71926 0x7CB5 Pickup 5 3000 1 x CT F13 1000 2 Y Y
71928 0x7CB7 Curve 0 21 1 FC161 2 1 Y Y
71929 0x7CB8 TDM 5 60000 1 F2 100 1 Y Y
71930 0x7CB9 Reset 0 1 1 FC265 0 1 Y Y
71931 0x7CBA Direction 0 2 1 FC164 0 1 Y Y
71932 0x7CBB Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
71934 0x7CBD Block 0 0xC6CD00 1 FC142 0 2 Y Y
71936 0x7CBF Events 0 1 1 FC126 1 1 Y Y
71937 0x7CC0 Targets 0 2 1 FC101 1 1 Y Y
71938 0x7CC1 Pickup 50 1500 1 A F2 1000 1 Y
Sensitive Ground TOC 2
71952 0x7CCF Function 0 4 1 FC100 0 1 Y
71954 0x7CD1 Input 0 1 1 FC256 0 1 Y
71955 0x7CD2 Pickup 5 3000 1 x CT F13 1000 2 Y
71957 0x7CD4 Curve 0 21 1 FC161 2 1 Y
71958 0x7CD5 TDM 5 60000 1 F2 100 1 Y
71959 0x7CD6 Reset 0 1 1 FC265 0 1 Y
71960 0x7CD7 Direction 0 2 1 FC164 0 1 Y
71961 0x7CD8 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
71963 0x7CDA Block 0 0xC6CD00 1 FC142 0 2 Y
71965 0x7CDC Events 0 1 1 FC126 1 1 Y
71966 0x7CDD Targets 0 2 1 FC101 1 1 Y
Sensitive Ground IOC 1
72053 0x7D34 Function 0 4 1 FC100 0 1 Y Y
72056 0x7D37 Pickup 5 3000 1 x CT F13 1000 2 Y
72058 0x7D39 Direction 0 2 1 FC164 0 1 Y Y
72059 0x7D3A Pickup Delay 0 6000000 1 s F13 0 2 Y Y
72061 0x7D3C Dropout Delay 0 6000000 1 s F13 0 2 Y Y
72063 0x7D3E Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
72065 0x7D40 Block 0 0xC6CD00 1 FC142 0 2 Y Y
72067 0x7D42 Events 0 1 1 FC126 1 1 Y Y
72068 0x7D43 Targets 0 2 1 FC101 1 1 Y Y
72069 0x7D44 Pickup 50 1500 1 A F2 1000 1 Y
Sensitive Ground IOC 2
72083 0x7D52 Function 0 4 1 FC100 0 1 Y
72086 0x7D55 Pickup 5 3000 1 x CT F13 1000 2 Y
72088 0x7D57 Direction 0 2 1 FC164 0 1 Y
72089 0x7D58 Pickup Delay 0 6000000 1 s F13 0 2 Y
72091 0x7D5A Dropout Delay 0 6000000 1 s F13 0 2 Y
72093 0x7D5C Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
72095 0x7D5E Block 0 0xC6CD00 1 FC142 0 2 Y
72097 0x7D60 Events 0 1 1 FC126 1 1 Y
72098 0x7D61 Targets 0 2 1 FC101 1 1 Y
Sensitive Ground IOC 3
72113 0x7D70 Function 0 4 1 FC100 0 1 Y