13-284 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
77799 0x93A6 Targets 0 2 1 FC101 1 1 Y
Overfrequency 11
77813 0x93B4 Function 0 4 1 FC100 0 1 Y
77814 0x93B5 Signal Input 0x12 0x28 1 FC103A 0x12 1 Y
77815 0x93B6 Pickup 2000 6500 1 Hz F2 6050 1 Y
77816 0x93B7 Pickup Delay 0 6000000 1 s F13 5000 2 Y
77818 0x93B9 Dropout Delay 0 6000000 1 s F13 5000 2 Y
77820 0x93BB Minimum Voltage 0 1250 1 x VT F13 300 2 Y
77822 0x93BD Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
77824 0x93BF Block 0 0xC6CD00 1 FC142 0 2 Y
77826 0x93C1 Events 0 1 1 FC126 1 1 Y
77827 0x93C2 Targets 0 2 1 FC101 1 1 Y
Overfrequency 12
77841 0x93D0 Function 0 4 1 FC100 0 1 Y
77842 0x93D1 Signal Input 0x12 0x28 1 FC103A 0x12 1 Y
77843 0x93D2 Pickup 2000 6500 1 Hz F2 6050 1 Y
77844 0x93D3 Pickup Delay 0 6000000 1 s F13 5000 2 Y
77846 0x93D5 Dropout Delay 0 6000000 1 s F13 5000 2 Y
77848 0x93D7 Minimum Voltage 0 1250 1 x VT F13 300 2 Y
77850 0x93D9 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y
77852 0x93DB Block 0 0xC6CD00 1 FC142 0 2 Y
77854 0x93DD Events 0 1 1 FC126 1 1 Y
77855 0x93DE Targets 0 2 1 FC101 1 1 Y
Frequency Rate Of Change 1
78053 0x94A4 Function 0 4 1 FC100 0 1 Y Y Y Y
78054 0x94A5 Trend 0 2 1 FC253 0 1 Y Y Y Y
78055 0x94A6 Pickup 10 1500 1 Hz/sec F2 50 1 Y Y Y Y
78056 0x94A7 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
78058 0x94A9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y Y Y Y
78059 0x94AA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y Y Y Y
78060 0x94AB VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y Y Y
78061 0x94AC Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y Y Y
78063 0x94AE CT Input 1 5 1 FC102A 1 1 Y Y
78064 0x94AF Minimum Current 0 30000 1 x CT F13 200 2 Y Y Y Y
78066 0x94B1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
78068 0x94B3 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
78070 0x94B5 Events 0 1 1 FC126 1 1 Y Y Y Y
78071 0x94B6 Targets 0 2 1 FC101 1 1 Y Y Y Y
Frequency Rate Of Change 2
78085 0x94C4 Function 0 4 1 FC100 0 1 Y Y Y Y
78086 0x94C5 Trend 0 2 1 FC253 0 1 Y Y Y Y
78087 0x94C6 Pickup 10 1500 1 Hz/sec F2 50 1 Y Y Y Y
78088 0x94C7 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y Y Y
78090 0x94C9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y Y Y Y
78091 0x94CA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y Y Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5

Table of Contents