CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-285
78092 0x94CB VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y Y Y
78093 0x94CC Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y Y Y
78095 0x94CE CT Input 1 5 1 FC102A 1 1 Y Y
78096 0x94CF Minimum Current 0 30000 1 x CT F13 200 2 Y Y Y Y
78098 0x94D1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
78100 0x94D3 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
78102 0x94D5 Events 0 1 1 FC126 1 1 Y Y Y Y
78103 0x94D6 Targets 0 2 1 FC101 1 1 Y Y Y Y
Frequency Rate Of Change 3
78117 0x94E4 Function 0 4 1 FC100 0 1 Y Y
78118 0x94E5 Trend 0 2 1 FC253 0 1 Y Y
78119 0x94E6 Pickup 10 1500 1 Hz/sec F2 50 1 Y Y
78120 0x94E7 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y
78122 0x94E9 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y Y
78123 0x94EA Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y Y
78124 0x94EB VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y
78125 0x94EC Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y
78127 0x94EE CT Input 1 5 1 FC102A 1 1 Y Y
78128 0x94EF Minimum Current 0 30000 1 x CT F13 200 2 Y Y
78130 0x94F1 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
78132 0x94F3 Block 0 0xC6CD00 1 FC142 0 2 Y Y
78134 0x94F5 Events 0 1 1 FC126 1 1 Y Y
78135 0x94F6 Targets 0 2 1 FC101 1 1 Y Y
Frequency Rate Of Change 4
78149 0x9504 Function 0 4 1 FC100 0 1 Y Y
78150 0x9505 Trend 0 2 1 FC253 0 1 Y Y
78151 0x9506 Pickup 10 1500 1 Hz/sec F2 50 1 Y Y
78152 0x9507 Pickup Delay 0 6000000 1 s F13 2000 2 Y Y
78154 0x9509 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y Y
78155 0x950A Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y Y
78156 0x950B VT Input 0x12 0x28 1 FC103B 0x12 1 Y Y
78157 0x950C Minimum Voltage 0 1250 1 x VT F13 700 2 Y Y
78159 0x950E CT Input 1 5 1 FC102A 1 1 Y Y
78160 0x950F Minimum Current 0 30000 1 x CT F13 200 2 Y Y
78162 0x9511 Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y
78164 0x9513 Block 0 0xC6CD00 1 FC142 0 2 Y Y
78166 0x9515 Events 0 1 1 FC126 1 1 Y Y
78167 0x9516 Targets 0 2 1 FC101 1 1 Y Y
Frequency Rate Of Change 5
78181 0x9524 Function 0 4 1 FC100 0 1 Y
78182 0x9525 Trend 0 2 1 FC253 0 1 Y
78183 0x9526 Pickup 10 1500 1 Hz/sec F2 50 1 Y
78184 0x9527 Pickup Delay 0 6000000 1 s F13 2000 2 Y
78186 0x9529 Minimum Frequency 2000 8000 1 Hz F2 4500 1 Y
78187 0x952A Maximum Frequency 2000 8000 1 Hz F2 6500 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5