13-310 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
84801 0xAF00 Freeze/Count 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84803 0xAF02 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84805 0xAF04 HI 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84807 0xAF06 EQL 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84809 0xAF08 LO 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84811 0xAF0A Events 0 1 1 FC126 1 1 Y Y Y Y
Harmonic Detection 1
84830 0xAF1D Function 0 4 1 FC100A 0 1 Y Y Y Y
84831 0xAF1E Signal Input 1 5 1 FC102A 1 1 Y Y Y
84832 0xAF1F Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84833 0xAF20 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84834 0xAF21 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84836 0xAF23 Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84837 0xAF24 Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84838 0xAF25 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84840 0xAF27 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84842 0xAF29 Events 0 1 1 FC126 1 1 Y Y Y Y
84843 0xAF2A Targets 0 2 1 FC101 1 1 Y Y Y Y
Harmonic Detection 2
84854 0xAF35 Function 0 4 1 FC100A 0 1 Y Y Y Y
84855 0xAF36 Signal Input 1 5 1 FC102A 1 1 Y Y Y
84856 0xAF37 Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84857 0xAF38 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84858 0xAF39 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84860 0xAF3B Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84861 0xAF3C Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84862 0xAF3D Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84864 0xAF3F Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84866 0xAF41 Events 0 1 1 FC126 1 1 Y Y Y Y
84867 0xAF42 Targets 0 2 1 FC101 1 1 Y Y Y Y
Harmonic Detection 3
84878 0xAF4D Function 0 4 1 FC100A 0 1 Y Y Y Y
84879 0xAF4E Signal Input 1 5 1 FC102A 1 1 Y Y Y
84880 0xAF4F Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84881 0xAF50 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84882 0xAF51 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84884 0xAF53 Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84885 0xAF54 Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84886 0xAF55 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84888 0xAF57 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84890 0xAF59 Events 0 1 1 FC126 1 1 Y Y Y Y
84891 0xAF5A Targets 0 2 1 FC101 1 1 Y Y Y Y
Harmonic Detection 4
84902 0xAF65 Function 0 4 1 FC100A 0 1 Y Y Y Y
84903 0xAF66 Signal Input 1 5 1 FC102A 1 1 Y Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words