CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-311
84904 0xAF67 Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84905 0xAF68 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84906 0xAF69 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84908 0xAF6B Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84909 0xAF6C Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84910 0xAF6D Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84912 0xAF6F Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84914 0xAF71 Events 0 1 1 FC126 1 1 Y Y Y Y
84915 0xAF72 Targets 0 2 1 FC101 1 1 Y Y Y Y
Harmonic Detection 5
84926 0xAF7D Function 0 4 1 FC100A 0 1 Y Y Y Y
84927 0xAF7E Signal Input 1 5 1 FC102A 1 1 Y Y Y
84928 0xAF7F Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84929 0xAF80 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84930 0xAF81 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84932 0xAF83 Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84933 0xAF84 Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84934 0xAF85 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84936 0xAF87 Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84938 0xAF89 Events 0 1 1 FC126 1 1 Y Y Y Y
84939 0xAF8A Targets 0 2 1 FC101 1 1 Y Y Y Y
Harmonic Detection 6
84950 0xAF95 Function 0 4 1 FC100A 0 1 Y Y Y Y
84951 0xAF96 Signal Input 1 5 1 FC102A 1 1 Y Y Y
84952 0xAF97 Harmonic 0 4 1 FC374 0 1 Y Y Y Y
84953 0xAF98 Pickup 1 1000 1 % F1 200 1 Y Y Y Y
84954 0xAF99 Pickup Delay 0 60000000 1 s F13 0 2 Y Y Y Y
84956 0xAF9B Phases for Operation 0 3 1 FC261A 0 1 Y Y Y Y
84957 0xAF9C Minimum Oper Current 3 100 1 x CT F2 10 1 Y Y Y Y
84958 0xAF9D Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
84960 0xAF9F Output Relays 0 0xFFFFFFFF 1 FC198 0 2 Y Y Y Y
84962 0xAFA1 Events 0 1 1 FC126 1 1 Y Y Y Y
84963 0xAFA2 Targets 0 2 1 FC101 1 1 Y Y Y Y
Speed
85130 0xB049 Trip Function 0 4 1 FC100D 0 1 Y Y
85131 0xB04A Input 0 0x21F 1 FC266 0 2 Y Y
85133 0xB04C Rated Speed 100 7200 1 RPM F0 3600 1 Y Y
85134 0xB04D Pulses Per Rev 1 6 1 PPR F0 1 1 Y Y
85135 0xB04E Direction 0 1 1 FC381 0 1 Y Y
85136 0xB04F Trip Pickup 50 120 1 % F0 75 1 Y
85137 0xB050 Trip Pickup Delay 0 60000 1 s F2 110 1 Y
85138 0xB051 Trip Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y Y
85140 0xB053 Alarm Function 0 3 1 FC100E 0 1 Y Y
85141 0xB054 Alarm Pickup 50 120 1 % F0 80 1 Y Y
85142 0xB055 Alarm Pickup Delay 0 60000 1 s F2 100 1 Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words