13-312 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
85143 0xB056 Alarm Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y Y
85145 0xB058 Block 0 0xC6CD00 1 FC142 0 2 Y Y
85147 0xB05A Events 0 1 1 FC126 1 1 Y Y
85148 0xB05B Targets 0 2 1 FC101 1 1 Y Y
RTD 1 Input Setpoints
85400 0xB157 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85401 0xB158 Name 0 65535 1 F60_26 RTD 1 13 Y Y Y Y
85414 0xB165 Type 0 3 1 FC120 0 1 Y Y Y Y
85415 0xB166 Application 0 4 1 FC121 0 1 Y Y
85416 0xB167 Voting 0 18 1 FC122 0 1 Y Y
85417 0xB168 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85418 0xB169 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85419 0xB16A Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85420 0xB16B Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85422 0xB16D Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85423 0xB16E Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85424 0xB16F Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85425 0xB170 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85426 0xB171 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85429 0xB174 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85431 0xB176 Events 0 1 1 FC126 1 1 Y Y Y Y
85432 0xB177 Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 2 Input Setpoints
85433 0xB178 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85434 0xB179 Name 0 65535 1 F60_26 RTD 2 13 Y Y Y Y
85447 0xB186 Type 0 3 1 FC120 0 1 Y Y Y Y
85448 0xB187 Application 0 4 1 FC121 0 1 Y Y
85449 0xB188 Voting 0 18 1 FC122 0 1 Y Y
85450 0xB189 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85451 0xB18A Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85452 0xB18B Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85453 0xB18C Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85455 0xB18E Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85456 0xB18F Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85457 0xB190 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85458 0xB191 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85459 0xB192 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85462 0xB195 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85464 0xB197 Events 0 1 1 FC126 1 1 Y Y Y Y
85465 0xB198 Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 3 Input Setpoints
85466 0xB199 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85467 0xB19A Name 0 65535 1 F60_26 RTD 3 13 Y Y Y Y
85480 0xB1A7 Type 0 3 1 FC120 0 1 Y Y Y Y
85481 0xB1A8 Application 0 4 1 FC121 0 1 Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5