13-314 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
85558 0xB1F5 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85561 0xB1F8 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85563 0xB1FA Events 0 1 1 FC126 1 1 Y Y Y Y
85564 0xB1FB Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 6 Input Setpoints
85565 0xB1FC Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85566 0xB1FD Name 0 65535 1 F60_26 RTD 6 13 Y Y Y Y
85579 0xB20A Type 0 3 1 FC120 0 1 Y Y Y Y
85580 0xB20B Application 0 4 1 FC121 0 1 Y Y
85581 0xB20C Voting 0 18 1 FC122 0 1 Y Y
85582 0xB20D Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85583 0xB20E Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85584 0xB20F Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85585 0xB210 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85587 0xB212 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85588 0xB213 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85589 0xB214 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85590 0xB215 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85591 0xB216 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85594 0xB219 Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85596 0xB21B Events 0 1 1 FC126 1 1 Y Y Y Y
85597 0xB21C Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 7 Input Setpoints
85598 0xB21D Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85599 0xB21E Name 0 65535 1 F60_26 RTD 7 13 Y Y Y Y
85612 0xB22B Type 0 3 1 FC120 0 1 Y Y Y Y
85613 0xB22C Application 0 4 1 FC121 0 1 Y Y
85614 0xB22D Voting 0 18 1 FC122 0 1 Y Y
85615 0xB22E Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85616 0xB22F Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85617 0xB230 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85618 0xB231 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85620 0xB233 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85621 0xB234 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85622 0xB235 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85623 0xB236 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85624 0xB237 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85627 0xB23A Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85629 0xB23C Events 0 1 1 FC126 1 1 Y Y Y Y
85630 0xB23D Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 8 Input Setpoints
85631 0xB23E Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85632 0xB23F Name 0 65535 1 F60_26 RTD 8 13 Y Y Y Y
85645 0xB24C Type 0 3 1 FC120 0 1 Y Y Y Y
85646 0xB24D Application 0 4 1 FC121 0 1 Y Y