EasyManua.ls Logo

GE Multilin 869 - Page 437

Default Icon
870 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-315
85647 0xB24E Voting 0 18 1 FC122 0 1 Y Y
85648 0xB24F Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85649 0xB250 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85650 0xB251 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85651 0xB252 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85653 0xB254 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85654 0xB255 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85655 0xB256 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85656 0xB257 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85657 0xB258 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85660 0xB25B Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85662 0xB25D Events 0 1 1 FC126 1 1 Y Y Y Y
85663 0xB25E Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 9 Input Setpoints
85664 0xB25F Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85665 0xB260 Name 0 65535 1 F60_26 RTD 9 13 Y Y Y Y
85678 0xB26D Type 0 3 1 FC120 0 1 Y Y Y Y
85679 0xB26E Application 0 4 1 FC121 0 1 Y Y
85680 0xB26F Voting 0 18 1 FC122 0 1 Y Y
85681 0xB270 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85682 0xB271 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85683 0xB272 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85684 0xB273 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85686 0xB275 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85687 0xB276 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85688 0xB277 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85689 0xB278 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85690 0xB279 Alarm Relays 0 0xFFFFFFFF 1 FC198C 0 2 Y Y Y Y
85693 0xB27C Block 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
85695 0xB27E Events 0 1 1 FC126 1 1 Y Y Y Y
85696 0xB27F Targets 0 2 1 FC101 2 1 Y Y Y Y
RTD 10 Input Setpoints
85697 0xB280 Trip Function 0 4 1 FC100D 0 1 Y Y Y Y
85698 0xB281 Name 0 65535 1 F60_26 RTD 10 13 Y Y Y Y
85711 0xB28E Type 0 3 1 FC120 0 1 Y Y Y Y
85712 0xB28F Application 0 4 1 FC121 0 1 Y Y
85713 0xB290 Voting 0 18 1 FC122 0 1 Y Y
85714 0xB291 Trip Temperature 1 250 1 °C F0 155 1 Y Y Y Y
85715 0xB292 Trip Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85716 0xB293 Trip Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
85717 0xB294 Trip Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y Y Y Y
85719 0xB296 Alarm Function 0 3 1 FC100E 0 1 Y Y Y Y
85720 0xB297 Alarm Temperature 1 250 1 °C F0 130 1 Y Y Y Y
85721 0xB298 Alarm Pickup Delay 0 600 1 s F0 2 1 Y Y Y Y
85722 0xB299 Alarm Dropout Delay 0 600 1 s F0 0 1 Y Y Y Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5

Table of Contents