CHAPTER 13: MODBUS MEMORY MAP
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE 13-323
88119 0xBBF6 Change Inhibit 16 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88121 0xBBF8 Events 0 1 1 FC126 1 1 Y Y Y Y
Generator Field Brk Discrep
88140 0xBC0B Function 0 4 1 FC100 0 1 Y
88141 0xBC0C Assign Digital Input 0 0xC6CD00 1 FC142 0 2 Y
88143 0xBC0E Field Status Contact 0 1 1 FC177 0 1 Y
88144 0xBC0F Pickup Delay 10 60000 1 s F2 100 1 Y
88145 0xBC10 Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
88147 0xBC12 Block 0 0xC6CD00 1 FC142 0 2 Y
88149 0xBC14 Events 0 1 1 FC126 0 1 Y
88150 0xBC15 Targets 0 2 1 FC101 1 1 Y
Generator Seq. Shutdown
88170 0xBC29 Function 0 4 1 FC100 0 1 Y
88171 0xBC2A Arming Input 0 0xC6CD00 1 FC142 0 2 Y
88173 0xBC2C Power Direction 1 2 1 FC164A 1 1 Y
88174 0xBC2D Pickup MW Level 2 99 1 x Rated F2 5 1 Y
88175 0xBC2E Pickup Delay 20 18000 1 s F2 1000 1 Y
88176 0xBC2F Output Relay 0 0xFFFFFFFF 1 FC198 0 2 Y
88178 0xBC31 Block 0 0xC6CD00 1 FC142 0 2 Y
88180 0xBC33 Events 0 1 1 FC126 0 1 Y
88181 0xBC34 Targets 0 2 1 FC101 1 1 Y
Motor Thermal Inhibit
88210 0xBC51 Function 0 1 1 FC126 0 1 Y
88211 0xBC52 TC Used Margin 0 25 1 % F0 25 1 Y
Maximum Starting Rate
88230 0xBC65 Function 0 1 1 FC126 0 1 Y
88231 0xBC66 Interval 1 300 1 min F0 60 1 Y
88232 0xBC67 Max Number of Starts 1 16 1 F0 3 1 Y
88233 0xBC68 Events 0 1 1 FC126 1 1 Y
88234 0xBC69 Targets 0 2 1 FC101 2 1 Y
Time Between Starts
88250 0xBC79 Function 0 1 1 FC126 0 1 Y
88251 0xBC7A Minimum Time 0 600 1 min F0 10 1 Y
88252 0xBC7B Events 0 1 1 FC126 1 1 Y
88253 0xBC7C Targets 0 2 1 FC101 2 1 Y
Motor Start Supervision Restart Delay
88270 0xBC8D Function 0 1 1 FC126 0 1 Y
88271 0xBC8E Minimum Time 0 65000 1 s F0 0 1 Y
88272 0xBC8F Events 0 1 1 FC126 1 1 Y
88273 0xBC90 Targets 0 2 1 FC101 2 1 Y
Reduced Voltage Starting
88290 0xBCA1 Function 0 4 1 FC100D 0 1 Y
88291 0xBCA2 Control Output Relays 0 0xFFFFFFFF 1 FC198E 0 2 Y
88293 0xBCA4 Transition Mode 0 2 1 FC373 0 1 Y
88294 0xBCA5 Start Level Current 25 300 1 x FLA F2 125 1 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5