13-324 8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
88295 0xBCA6 Start Timer 10 6000 1 s F1 100 1 Y
88296 0xBCA7 Block 0 0xC6CD00 1 FC142 0 2 Y
88298 0xBCA9 Trip Output Relays 0 0xFFFFFFFF 1 FC198D 0 2 Y
88300 0xBCAB Events 0 1 1 FC126 1 1 Y
88301 0xBCAC Targets 0 2 1 FC101 2 1 Y
Local Control Mode
88320 0xBCBF Select Before Operate 0 1 1 FC126 0 1 Y Y Y Y
88321 0xBCC0 Local Mode 0 0xC6CD00 1 FC142 0x0001 2 Y Y Y Y
88323 0xBCC2 Bkr/Sw Select Timeout 1 10 1 min F0 5 1 Y Y Y Y
88324 0xBCC3 Cnct/Sw Select Timeout 1 10 1 min F0 5 1 Y
88325 0xBCC4 BKR Local Open 0 0x803A02 1 FC322 0x802802 2 Y Y Y Y
88327 0xBCC6 Contactor Local Open 0 0x803A02 1 FC322 0x802802 2 Y
88329 0xBCC8 BKR Local Close 0 0x803A02 1 FC322 0x802A02 2 Y Y Y Y
88331 0xBCCA Contactor Local Close 0 0x803A02 1 FC322 0x802A02 2 Y
88333 0xBCCC SW Local Open 0 0x803A02 1 FC322 0x802802 2 Y Y Y Y
88335 0xBCCE SW Local Close 0 0x803A02 1 FC322 0x802A02 2 Y Y Y Y
88337 0xBCD0 Tagging 0 1 1 FC126 1 1 Y Y Y Y
88338 0xBCD1 Events 0 1 1 FC126 0 1 Y Y Y Y
88339 0xBCD2 Targets 0 2 1 FC101 1 1 Y Y Y Y
BKR 1 Control
88350 0xBCDD Remote Open 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88352 0xBCDF Remote Close 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88354 0xBCE1 Remote Block Open 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88356 0xBCE3 Remote Block Close 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88358 0xBCE5 Bypass Rem Blk Open 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88360 0xBCE7 Bypass Rem Blk Close 0 0xC6CD00 1 FC142 0 2 Y Y Y Y
88362 0xBCE9 Close Sync Spvn BKR1 0 2 1 FC410 0 1 Y Y Y Y
88363 0xBCEA Events 0 1 1 FC126 0 1 Y Y Y Y
88364 0xBCEB Targets 0 2 1 FC101 1 1 Y Y Y Y
BKR 2 Control
88365 0xBCEC Remote Open 0 0xC6CD00 1 FC142 0 2 Y Y Y
88367 0xBCEE Remote Close 0 0xC6CD00 1 FC142 0 2 Y Y Y
88369 0xBCF0 Remote Block Open 0 0xC6CD00 1 FC142 0 2 Y Y Y
88371 0xBCF2 Remote Block Close 0 0xC6CD00 1 FC142 0 2 Y Y Y
88373 0xBCF4 Bypass Rem Blk Open 0 0xC6CD00 1 FC142 0 2 Y Y Y
88375 0xBCF6 Bypass Rem Blk Close 0 0xC6CD00 1 FC142 0 2 Y Y Y
88377 0xBCF8 Close Sync Spvn BKR2 0 2 1 FC410 0 1 Y Y Y
88378 0xBCF9 Events 0 1 1 FC126 0 1 Y Y Y
88379 0xBCFA Targets 0 2 1 FC101 1 1 Y Y Y
BKR 3 Control
88380 0xBCFB Remote Open 0 0xC6CD00 1 FC142 0 2 Y
88382 0xBCFD Remote Close 0 0xC6CD00 1 FC142 0 2 Y
88384 0xBCFF Remote Block Open 0 0xC6CD00 1 FC142 0 2 Y
88386 0xBD01 Remote Block Close 0 0xC6CD00 1 FC142 0 2 Y
88388 0xBD03 Bypass Rem Blk Open 0 0xC6CD00 1 FC142 0 2 Y
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5

Table of Contents