GE Power Management 469 Motor Management Relay 6-35
6 COMMUNICATIONS 6.4 MEMORY MAP
6
O/L CURVE
SETUP
15AF Standard Overload Curve Number 1 15 1 - F1 4
15B0 Time to Trip at 1.01 x FLA 5 999999 1 s F10 174145
15B2 Time to Trip at 1.05 x FLA 5 999999 1 s F10 34149
15B4 Time to Trip at 1.10 x FLA 5 999999 1 s F10 16667
15B6 Time to Trip at 1.20 x FLA 5 999999 1 s F10 7954
15B8 Time to Trip at 1.30 x FLA 5 999999 1 s F10 5072
15BA Time to Trip at 1.40 x FLA 5 999999 1 s F10 3646
15BC Time to Trip at 1.50 x FLA 5 999999 1 s F10 2800
15BE Time to Trip at 1.75 x FLA 5 999999 1 s F10 1697
15C0 Time to Trip at 2.00 x FLA 5 999999 1 s F10 1166
15C2 Time to Trip at 2.25 x FLA 5 999999 1 s F10 861
15C4 Time to Trip at 2.50 x FLA 5 999999 1 s F10 666
15C6 Time to Trip at 2.75 x FLA 5 999999 1 s F10 533
15C8 Time to Trip at 3.00 x FLA 5 999999 1 s F10 437
15CA Time to Trip at 3.25 x FLA 5 999999 1 s F10 366
15CC Time to Trip at 3.50 x FLA 5 999999 1 s F10 311
15CE Time to Trip at 3.75 x FLA 5 999999 1 s F10 268
15D0 Time to Trip at 4.00 x FLA 5 999999 1 s F10 233
15D2 Time to Trip at 4.25 x FLA 5 999999 1 s F10 205
15D4 Time to Trip at 4.50 x FLA 5 999999 1 s F10 182
15D6 Time to Trip at 4.75 x FLA 5 999999 1 s F10 162
15D8 Time to Trip at 5.00 x FLA 5 999999 1 s F10 146
15DA Time to Trip at 5.50 x FLA 5 999999 1 s F10 120
15DC Time to Trip at 6.00 x FLA 5 999999 1 s F10 100
15DE Time to Trip at 6.50 x FLA 5 999999 1 s F10 85
15E0 Time to Trip at 7.00 x FLA 5 999999 1 s F10 73
15E2 Time to Trip at 7.50 x FLA 5 999999 1 s F10 63
15E4 Time to Trip at 8.00 x FLA 5 999999 1 s F10 56
15E6 Time to Trip at 10.0 x FLA 5 999999 1 s F10 56
15E8 Time to Trip at 15.0 x FLA 5 999999 1 s F10 56
15EA Time to Trip at 20.0 x FLA 5 999999 1 s F10 56
15EC Reserved
...
15FF Reserved
1600 Minimum Allowable Line Voltage 70 95 1 %Rated F1 80
1601 Stall Current at Min Vline 200 1500 1
×
FLA F3 480
1602 Safe Stall Time at Min Vline 5 9999 1 s F2 200
1603 Accel. Intersect at Min Vline 200 1500 1
×
FLA F3 380
1604 Stall Current at 100% Vline 200 1500 1
×
FLA F3 600
1605 Safe Stall Time at 100% Vline 5 9999 1 s F2 100
1606 Accel. Intersect at 100% Vline 200 1500 1
×
FLA F3 500
1607 Reserved
Table 6–1: 469 MEMORY MAP (Sheet 18 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT