GE Power Management 469 Motor Management Relay 6-37
6 COMMUNICATIONS 6.4 MEMORY MAP
6
CURRENT
UNBALANCE
1680 Current Unbalance Alarm 0 2 1 - FC115 0
1681 Current Unbalance Alarm Relays 0 6 1 - FC113 0
1682 Current Unbalance Alarm Pickup 4 40 1 % F1 15
1683 Current Unbalance Alarm Delay 1 60 1 s F1 1
1684 Current Unbalance Alarm Events 0 1 1 - FC103 0
1685 Current Unbalance Trip 0 2 1 - FC115 0
1686 Current Unbalance Trip Relays 0 3 1 - FC111 0
1687 Current Unbalance Trip Pickup 4 40 1 % F1 20
1688 Current Unbalance Trip Delay 1 60 1 s F1 1
1689 Reserved
...
169F Reserved
GROUND
FAULT
16A0 Reserved
16A1 Ground Fault Alarm 0 2 1 - FC115 0
16A2 Ground Fault Alarm Relays 0 6 1 - FC113 0
16A3 Ground Fault Alarm Pickup 10 100 1
×
CT F3 10
16A4 Alarm Pickup for 50/0.025 CT 25 2500 1 A F3 100
16A5 Intentional GF Alarm Delay 0 1000 10 ms F1 0
16A6 Ground Fault Alarm Events 0 1 1 - FC103 0
16A7 Ground Fault Trip 0 2 1 - FC115 0
16A8 Ground Fault Trip Relays 0 6 1 - FC118 0
16A9 Ground Fault Trip Pickup 10 100 1
×
CT F3 20
16AA Trip Pickup for 50/0.025 CT 25 2500 1 A F3 100
16AB Intentional GF Trip Delay 0 1000 10 ms F1 0
16AC Ground Fault Trip Backup 0 1 1 - FC103 0
16AD Ground Fault Trip Backup Relays 0 2 1 - FC119 0
16AE Ground Fault Trip Backup Delay 10 2000 10 ms F1 200
... Reserved
16BF Reserved
PHASE
DIFFERENTIAL
16C0 Phase Differential Trip 0 2 1 - FC115 0
16C1 Phase Differential Trip Relays 0 6 1 - FC118 0
16C2 Differential Trip Pickup While Starting 5 100 1
×
CT F3 10
16C3 Differential Trip Delay While Starting 0 60000 10 ms F1 0
16C4 Differential Trip Pickup While Running 5 100 1
×
CT F3 10
16C5 Differential Trip Delay While Running 0 1000 10 ms F1 0
16C4 Reserved
...
16CF Reserved
Table 6–1: 469 MEMORY MAP (Sheet 20 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT