EasyManua.ls Logo

GE 745 - Page 114

GE 745
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5–18 745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTO-CONFIGURATION CHAPTER 5: SETPOINTS
Y/d330°/
d210°
1 WYE 330° lag Y/d330°/
d330°
1 WYE 330° lag
2DELTA
330° lag
2 DELTA
330° lag
3DELTA
210° lag
120° lag 3 DELTA
330° lag
D/d0°/d0° 1 DELTA D/d0°/d60° 1 DELTA 60° lag
2DELTA
2 DELTA
60° lag
3DELTA
3 DELTA
60° lag
D/d0°/d120° 1 DELTA 120° lag D/d0°/d180° 1 DELTA 180° lag
2DELTA
120° lag 2 DELTA
180° lag
3DELTA
120° lag
3 DELTA
180° lag
D/d0°/d240° 1 DELTA 240° lag D/d0°/d300° 1 DELTA 300° lag
2DELTA
240° lag 2 DELTA
300° lag
3DELTA
240° lag
3 DELTA
300° lag
D/d0°/y30° 1 DELTA D/d0°/y150° 1 DELTA
2DELTA
2 DELTA
3WYE
30° lag
330° lag 3 WYE
150° lag
210° lag
Table 5–1: Transformer types (Sheet 6 of 11)
Transformer
type
Wdg. Connection Voltage
phasors
Phase
shift
Transformer
type
Wdg. Connection Voltage
phasors
Phase
shift