EasyManua.ls Logo

GE 745 - M Iscellaneous

GE 745
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2–10 745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS CHAPTER 2: OVERVIEW
2.2.5 Miscellaneous
COMMUNICATIONS
All ports:..............................................................300 to 19200 baud, programmable parity, Modbus RTU
protocol, DNP
Ethernet: .............................................................With order code T only,
10Base-T RJ45 connector,
Modbus TCP/IP
Version 2.0 / IEEE 802.3
RS232:..................................................................Front panel,
9-pin D connector
RS485/RS422 (COM1)....................................Back panel
RS485 second port (COM2)........................Back panel, with order code E only.
CLOCK
Resolution: .........................................................1 ms
Accuracy.............................................................±1 ms with IRIG-B
±1 minute/month without IRIG-B
Supercap backup life:...................................45 days when control power is off
HARMONICS
Range:..................................................................0.00 to 99.9%
Accuracy:...............................................±1% of full-scale at 0.5 × CT
THD
Range:..................................................................0.00 to 99.9%
Accuracy:...........................................................±1% of full-scale at 0.5 × CT
EVENT RECORDER
Number of events: .........................................256
Event content:..................................................see Types and causes of events on page 6–19
OPERATING ENVIRONMENT
Operating temperature:.............................. –40°C to +60°C
Storage temperature:...................................–40°C to +80°C ambient
Humidity:............................................................up to 90% non-condensing
Altitude:...............................................................2000 m
Pollution degree:.............................................II
CASE
Drawout:.............................................................Fully drawout unit (automatic CT shorts)
Voltage Break Maximum load
DC resistive 30 V DC 10 A 300 W
125 V DC 0.5 A 62.5 W
250 V DC 0.3 A 75 W
DC inductive
L/R = 40 ms
30 V DC 5 A 150 W
125 V DC 0.25 A 31.3 W
250 V DC 0.15 A 37.5 W
AC resistive 120 V AC 10 A 2770 VA
240 V AC 10 A 2770 VA
AC inductive
PF = 0.4
120 V AC 4 A 480 VA
240 V AC 3 A 750 VA