7–54 745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION SCHEMES CHAPTER 7: COMMISSIONING
7.5.19 Insulation Aging
7.5.19.1 Description
The three elements under the insulation aging feature, hottest-spot limit, aging factor limit,
and loss of life limit, must be tested with a valid set of transformer data programmed into
the relay. The ambient temperature must also be programmed (obtained from an RTD or
programmed as 12-month averages). The tests consist of simulating transformer loading
by applying a current signal to winding 1 phase A at the correct frequency.
7.5.19.2 Hottest-spot Limit
The hottest-spot temperature value is a function of load, ambient temperature, and
transformer rating.
Apply a current to winding 1 phase A to represent at least a 100% load
on the transformer.
Use the A2 METERING
 LOSS OF LIFE HOTTEST-SPOT
WINDING TEMPERATURE actual value to observe the hottest spot
temperature increases gradually. The simulated load to may be increased
for a faster temperature rise.
When the hottest spot temperature reaches the
S4 ELEMENTS  INSULATION AGING
HOTTEST-SPOT LIMIT
 HOTTEST-SPOT LIMIT PICKUP operating level, the element should
operate.
Verify all programmed relay operations as per FlexLogic™ settings.
Verify that all the targets and messages are as expected and
programmed.
The time delay can be verified with a watch as the delay is normally set in minutes.
7.5.19.3 Aging Factor Limit
The Aging Factor value is also a function of load, ambient temperature, and transformer
ratings.
Apply a current to Winding 1 Phase A to represent at least a 100%
transformer load.
Use the A2 METERING
 LOSS OF LIFE  INSULATION AGING
FACTOR actual value to observe that the aging factor increases
gradually.
You may want to increase the simulated load or the simulated or
programmed ambient temperature to cause a faster increase.
When the aging factor reaches the
S4 ELEMENTS  INSULATION AGING  AGING
FACTOR LIMIT
 AGING FACTOR LIMIT PICKUP operating level, the element should
operate.
Verify all programmed relay operations as per FlexLogic™ settings.
Verify that all the targets and messages are as expected and
programmed.
The time delay can be verified with a watch as the delay is normally set in minutes.