1–6 EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 1: OVERVIEW
1.4 Specifications
1.4.1 Inputs/Outputs
POWER SUPPLY
Range:..................................................................D2 Option: Universal, 90 to 265 V AC at 50/60Hz, or 100 to
370 V DC
D Option: 18 to 60 V DC
Power consumption:.....................................5 VA, 3.5 W
VOLTAGE INPUTS (MEASUREMENT CATEGORY III)
Range:..................................................................Universal, Auto-ranging up to 416 V AC L-N, 721 V AC L-L
Supported hookups:......................................3-element Wye, 2.5-element Wye, 2-element Delta,
4-wire Delta
Input impedance:...........................................1 MOhm/phase
Burden:................................................................0.0144 VA/phase at 120 Volts
Pickup voltage: ................................................10 V AC
Connection:.......................................................Screw terminal (see Voltage Connection on page 3–8)
Maximum input wire gauge: ....................AWG #12 / 2.5 mm
2
Fault withstand: ..............................................Meets IEEE C37.90.1
Reading:..............................................................Programmable full-scale to any PT ratio
CURRENT INPUTS
Class 10:..............................................................5 A nominal, 10 A maximum
Class 2: ................................................................1 A nominal, 2 A maximum
Burden:................................................................0.005 VA per phase maximum at 11 A
Pickup current:.................................................0.1% of nominal
Connections:.....................................................O or U lug (see CT Leads Terminated to Meter on page 3–
6);
Pass-through wire, 0.177" / 4.5 mm maximum diameter
(see Pass-Through Wire Electrical Connection on page
3–7);
Quick connect, 0.25" male tab
(see Quick Connect Electrical Connection on page 3–7)
Fault Withstand:..............................................100 A / 10 seconds, 300 A / 3 seconds, 500 A / 1 second
Reading:..............................................................Programmable full-scale to any CT ratio
1.4.2 Metering
MEASUREMENT METHODS
Voltage and current:.....................................true RMS
Power:..................................................................sampling at 400+ samples/cycle on all channels
measured; readings simultaneously
A/D conversion:...............................................6 simultaneous 24-bit analog-to-digital converters
UPDATE RATE
Watts, vars, and VA: ......................................100 ms (10 times per second)
All other parameters:....................................1 second

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin EPM 6000 and is the answer not in the manual?

GE Multilin EPM 6000 Specifications

General IconGeneral
BrandGE
ModelMultilin EPM 6000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals