CHAPTER 4: USING THE METER
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 4–13
This will display the and the Pt-n (PT numerator) screen.
Z Press ENTER again to change to display the
Pt-d (PT denominator)
screen.
Z Press ENTER again to select the to Pt-S (PT scaling) value.
The
Pt-S value can be “1, “10”, or “100”. Refer to Programming the Configuration Mode
Screens on page 4–10 for instructions on changing values.
Example settings for the
Pt-n, Pt-d, and Pt-S values are shown below:
14400/120 V (reads 14400 V): set
Pt-n to “1440”, Pt-d to “120”, and Pt-S
to “10”
138000/69 V (reads 138000 V): set
Pt-n to “1380”, Pt-d to “69”, and Pt-S
to “100”
345000/115 V (reads 347000 V): set
Pt-n to “3450”, Pt-d to “115”, and
Pt-S to “100”
Z Press ENTER to scroll through the other
CFG parameters.
Z Press DOWN or RIGHT to display the password screen (see Reset
Mode and Password Entry on page 4–6 for details).
Z Press MENU to return to the main configuration menu.
Note
Pt-n and Pt-S are dictated by primary voltage. Pt-d is secondary voltage.
4.3.6 Configuring the Connection Setting
Use the following procedure to program the connection (Cnct) setting.