CHAPTER 4: USING THE METER
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 4–11
The Stor ALL donE message will appear and the meter will reset.
4.3.4 Configuring the CT Setting
Use the following procedure to program the CT setting.
Z Push the DOWN Button to scroll through the configuration mode
parameters.
Press ENTER when
Ct is the active parameter (i.e. it is in the “A” screen and flashing).
This will display the and the
Ct-n (CT numerator) screen.
Z Press ENTER again to change to display the
Ct-d (CT denominator)
screen.
The Ct-d value is preset to a 1 or 5 A at the factory and cannot be changed.