EasyManua.ls Logo

GE MultiLink ML1200

GE MultiLink ML1200
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7–8 MULTILINK ML1200 MANAGED FIELD SWITCH – INSTRUCTION MANUAL
ACCESS USING RADIUS CHAPTER 7: ACCESS USING RADIUS
Setting port control parameters (continued)
ML1200(auth)##
reauth port=1 status=enable period=300
Successfully set re-authentication parameter(s)
ML1200(auth)## shoW-port reauth
Port Reauth Status Reauth Period (sec.)
=========================================
1 Enabled 300
2 Enabled 3600
3 Enabled 3600
4 Enabled 3600
5 Enabled 3600
6 Enabled 3600
ML1200(auth)## show-stats port=3
Port 3 Authentication Counters
authEntersConnecting : 3
authEapLogoffsWhileConnecting : 0
authEntersAuthenticating : 3
authAuthSuccessesWhileAuthenticating : 2
authAuthTimeoutsWhileAuthenticating : 0
authAuthFailWhileAuthenticating : 0
authAuthReauthsWhileAuthenticating : 0
authAuthEapStartsWhileAuthenticating : 1
authAuthEapLogoffWhileAuthenticating : 0
authAuthReauthsWhileAuthenticated : 0
authAuthEapStartsWhileAuthenticated : 0
authAuthEapLogoffWhileAuthenticated : 0
backendResponses : 5
backendAccessChallenges : 2
backendOtherRequestsToSupplicant : 0
backendNonNakResponsesFromSupplicant : 2
backendAuthSuccesses : 2
backendAuthFails : 0
ML1200(auth)## trigger-reauth port=3
Successfully triggered re-authentication
ML1200(auth)##
This command forces the
authentication period on port #1
every 5 minutes; all other ports are
force authenticated every hour as
indicated by the
show-port reauth
command below.

Table of Contents