7–12 MULTILINK ML1200 MANAGED FIELD SWITCH – INSTRUCTION MANUAL
ACCESS USING RADIUS CHAPTER 7: ACCESS USING RADIUS
The Max Reauth column shows the permitted reauthentication attempts before the port
becomes unauthorized. Values are integers ranging from 0 to 10, with a default of 2.
The Tx Period column represents the transmit period. This is the time (in seconds) the
authenticator waits to transmit another request for identification from the supplicant. The
values range from 1 to 65535 seconds, with a default of 30.
The backend or communication characteristics between the ML1200 and the RADIUS
Server are defined through the Configuration > Radius > Port > Access > Backend menu
item.
The Supp Timeout column represents the timeout the authenticator waits for the
supplicant to respond. The values range from 1 to 240 seconds, with a default of 30.
The Server Timeout column represents the timeout the authenticator waits for the
backend RADIUS server to respond. The values range from 1 to 240 seconds, with a default
of 30.
The Max Request column represents the maximum times the authenticator retransmits an
EAP request packet to the supplicant before it times out. Values are integers ranging from
1 to 10, with a default of 2.