116 ADV200 • Functions description and parameters list
The toolbar commands “Copyset0” and “Copyset1” are used, after opening a .gfe le where the two sets have been
stored, to load set 0 and set 1, respectively, to the parameter grid, without interacting with the drive. The previous contents of
the parameter grid (which will not necessarily have coincided with either set 0 or set 1) are lost. Use this command to nd out
which values will actually be sent to the drive.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.7.1 3300Parsetenable ENUM Disable 0 1 ERW FVS
Enabling of management of two parameter sets
0 Disable
1 Enable
When set to 0 only one parameter set is managed (the one used as the default set).
If set to 1 two separate parameter sets can be congured. These can be selected using a command signal on a
digital input of the terminal strip.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.7.2 3302Parsetselectsrc LINK 16 6000 0 16384 ERWZ FVS
Selection of the origin (source) of the signal to be used to select the parameter set. The terminal or digital
command that can be associated with this function can be selected from among those available in the “L_DIG-
SEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.7.3 3304Parsetselectmon ENUM 16 Set 0 0 0 ER FVS
The parameter set currently in use is displayed.
0 Set 0
1 Set 1
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
22.7.4 3306Parset0to1copy BIT 0 0 1 ERW FVS
Proceduresforsettingupandmanagingthedoubleparameterset
Creatingthesecondset:
This function copies parameter set 0 onto set 1. Before enabling management of the double parameter set, the
rst set should be programmed with the correct values.
When the rst set is ready, the second can be activated as follows:
1 Activate management of the double parameter set by enabling parameter 3300Parsetenable.
2 Copy set 0 onto set 1 using command 3306Parset0to1copy.
This creates an initial parameter base in set 1 to which changes can be made.
Save the parameters.
3 Activate set 1 using parameter 3302Parsetselectsrc.
To select set 1 manually, set this parameter to “One”.
Otherwise select the desired source.
4 Modify the parameters in set 1 as necessary.
5 Save the parameters.
You can change the set being used by changing the source selected in parameter 3302Parsetselectsrc.
This can only be changed with the drive disabled.
When the double parameter set is active, the number of the set being used is shown next to the number of
each parameter on the keypad.
Modifyingandsavingparameters:
When the double parameter set is active, any parameters that need to be the same in the two sets must be
modied in each set separately.
Parameters are only saved in the set that is active at the time. To save both sets, you must rst save one and
then select and save the other.
Note ! Any changes to the parameters regarding the “parameter sets”, performed when enabled, will be lost at the next switching unless
a Parset0to1copy command is sent. To save data permanently (even when the drive is switched off), send the Saveparam-
eters command (DRIVE CONFIG menu).