ADV200 • Functions description and parameters list 171
This parameter is active when the speed is below the threshold set in parameter 940Speed0threshold.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
946 Speedis0delay BIT 16 0 0 1 ER
This signal is active when the reference is below the threshold set in parameter940Speed0threshold. The
signal is activated after the delay set in parameter 942Speed0delay.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
956 Speedthr1_2mon BIT 16 0 0 1 ER
To display the speed threshold status: if the motor speed is higher than the value set in parameter 950 Speed
threshold1 or lower than the value set in parameter 952Speedthreshold2 this parameter assumes the
value of 0.
If the motor speed is between the value of 950 Speedthreshold1 and that of 952Speedthreshold2, this
parameter assumes the value of 1.
Use parameter 954Speedthresholddly to set a delay time for the transition from 0 to 1 of parameter 956
Speedthr1_2mon; the transition from 1 to 0 is always immediate.
When 950 Speedthreshold1 is set to a value higher than 952Speedthreshold2, if the motor speed is be-
tween the thresholds this parameter assumes the value of 1. If 950 Speedthreshold1 is set to a value lower
than 952Speedthreshold2, the threshold status is not signicant
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
966 Setspeed BIT 16 0 0 1 ER
This signal is active when the error between the speed reference and actual motor speed is greater than the
tolerance set in parameter 962Setspeederror.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
976 Speedthr3mon BIT 16 0 0 1 ER
The status of the block that detects exceeding of the speed 3 threshold is displayed.
0 Actual speed below threshold
1 Actual speed above threshold
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
986 Currentthrmon BIT 16 0 0 1 ER
The status of the block that detects exceeding of the current threshold is displayed.
0 Actual output current below threshold
1 Actual output current above threshold.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1030Local/remotemon BIT 16 0 0 1 ER
This signal is active when the drive is in the Remote operating mode.
0 Local
1 Remote
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1060Sequencerstatus UINT16 16 0 0 0 ER
This signal indicates the state of the “machine states” that controls drive operation.
STS_INIT 0
STS_MAGN 1
STS_STOP 2
STS_START 3
STS_FS_STOP 4