ADV200 • Functions description and parameters list 31
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
6.12 726 Multirampselmon UINT16 0 0 3 ER FVS
The set of acceleration/deceleration ramps selected using the digital inputs is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
6.13 730 Acceljerktime0 s FLOAT 1.0 0.02 10.0 ERW FVS
6.14 732 Deceljerktime0 s FLOAT 1.0 0.02 10.0 ERW FVS
6.15 734 Acceljerktime1 s FLOAT 1.0 0.02 10.0 ERW FVS
6.16 736 Deceljerktime1 s FLOAT 1.0 0.02 10.0 ERW FVS
6.17 738 Acceljerktime2 s FLOAT 1.0 0.02 10.0 ERW FVS
6.18 740 Deceljerktime2 s FLOAT 1.0 0.02 10.0 ERW FVS
6.19 742 Acceljerktime3 s FLOAT 1.0 0.02 10.0 ERW FVS
6.20 744 Deceljerktime3 s FLOAT 1.0 0.02 10.0 ERW FVS
Jerks are variations of acceleration in time. They are used when there is a need to dampen the beginning and
end of the ramp. The Jerk value is added, regardless of the variation in speed, to the linear ramp time.
f
t
ACC TIME DEC TIME
6.13 6.13 6.14 6.14
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
6.21 750 Rampinzerosrc LINK 16 6000 0 16384 ERW FVS
Selection of the origin (source) of the signal that blocks the ramp input and moves the reference to zero. If the
ramp input is enabled, the Rampref parameter corresponds to the set reference. If the ramp input is blocked,
the drive slows down with the set deceleration time until reaching zero speed. The terminal to be associated
with this function can be selected from the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
6.22 752 Rampoutzerosrc LINK 16 6000 0 16384 ERW FVS
Selection of the origin (source) of the signal that brings the ramp to 0 (Rampref1/Rampref2=0). When the
ramp output is set to zero using Rampoutzero, the drive brakes with the maximum available torque; in this
case the ramp is disabled. The terminal to be associated with this function can be selected from the “L_DIG-
SEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
6.23 754 Rampfreezesrc LINK 16 3480 0 16384 ERW FVS
Selection of the origin (source) of the signal that temporarily freezes the ramp output value, regardless of any
changes in the input reference. The terminal to be associated with this function can be selected from the “L_
DIGSEL2” selection list.