EasyManuals Logo

gefran ADV200 Functions Description And Parameters List

gefran ADV200
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
ADV200 Functions description and parameters list 95
stability.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.19 2312OverFluxspdthr rpm FLOAT 400 10.0 1000.0 ERW __S
Speed limit below which the overux value set in PAR 2308 OverFluxperc.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.20 2314Fluxstep FLOAT 20.0 1 2000 ERW __S
Setting of the ramp time in the transition between the rated ux and the overux value set in PAR 2308 Over-
Fluxperc.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.21 2320Magnetizationtime ms UINT16 256 128 4096 ERWZ FVS
This parameter is used to slow down the magnetisation transient and prevent the motor shaft from rotating due
to the alignment of the stator and rotor.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals